Heat Recovery Systems

CITY MULTI VRF - Indoor Units

PEFY (Low Profile)

Overview

The PEFY model is a high-performance, ceiling-concealed, ducted indoor unit. An excellent choice soffit applications in hotels or offices.

  • External static pressure settings are adjustable to meet different application conditions
  • Extremely quiet, with sound ratings as low as 26 dB(A)
  • Auto-fan feature to adjust fan speed based on temperature differentials between space and set point
  • Capacities range from 6,000 to 24,000 Btu/h
  • Side access to control panel
  • Integrated condensate lift mechanism to provide up to 21 11/16" of lift
Model Specifications
Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz
Cooling Capacity (Nominal) 6000 Btu/h (1.8 kW) *1
Power Input (Nominal) 0.05/0.05 kW *1
Heating Capacity (Nominal) 6700 Btu/h (2 kW) *1
Power Input (Nominal) 0.03/0.03 kW *1
Recommended Fuse/Breaker Size 0.52 Ampere
Refrigerant Type R410A
Fan Motor type DC motor
Airflow Rate 176-212-247 CFM (5-6-7 m³/min) *2
External Static Pressure (208V) 0.02 -0.06-0.14 -0.20 In. WG (5 -15-35 -50 Pa)
(230V) 0.02 -0.06-0.14 -0.20 In. WG (5 -15-35 -50 Pa)
Air Filter PP Honeycomb fabric (washable)
Sound Pressure Level (measured in anechoic room) 22-24-28 dB(A)
Dimensions H x W x D Height 7-7/8 Inches (200 mm)
Width 31-1/8 Inches (794 mm)
Depth 27-9/16 Inches (700 mm)
Net Weight 42 Lbs. (19 kg)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm) Brazed
Condensate Lift Mechanism (Standard) 21-4/16 in
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Operating Temperature Range Cooling (Outdoor) 95°F (35°C) DB
Heating (Outdoor) 47°F (8°C) DB / 43°F (6°C) WB