Heat Pump Systems

CITY MULTI VRF - Indoor Units

PLFY

Overview

 

The PLFY-Series four-way ceiling-recessed cassette provides exceptional performance and excellent air coverage. Two styles are available - the PLFY-P-NBMU and the PLFY-P-NCMU.

 

PLFY-NBMU Features:

• 33 x 33" cabinet size

• Capacity range of 12,000 to 36,000 Btu/h

• Sound levels as low as 27 dB(A)

• Ventilation air connection

• High-efficiency filter option

• Branch ducting capability

• Auto-fan feature to adjust fan speed based on temperature differentials between space and set point

• Integrated condensate lift mechanism to provide up to 33 1/2" of lift

 

PLFY-NCMU Features:

• 24 x 24" cabinet size to fit in standard T-grid ceiling

• Capacity range of 8,000 to 15,000 Btu/h

• Sound levels as low as 29 dB(A)

• Ventilation air connection

• Auto-fan feature to adjust fan speed based on temperature differentials between space and set point

• Integrated condensate lift mechanism to provide up to 19 11/16" of lift

 

Model Specifications
Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz
Cooling Capacity (Nominal) 8000 Btu/h (2.3 kW) *1
Power Input (Nominal) 0.05 kW *1
Heating Capacity (Nominal) 9000 Btu/h (2.6 kW) *1
Power Input (Nominal) 0.05 kW *1
Refrigerant Type R410A
Fan Motor type 1-phase induction motor
Airflow Rate 280-320-350 CFM (8.0-9.0-10.0 m³/min) *3
External Static Pressure (208V) 0 In. WG (0 Pa)
(230V) 0 In. WG (0 Pa)
Sound Pressure Level (measured in anechoic room) 29-32-38 dB(A)
Dimensions H x W x D Height 8-3/16 Inches (208 mm)
Width 22-7/16 Inches (570 mm)
Depth 22-7/16 Inches (570 mm)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm) Flare
Liquid (High Pressure) 1/4 Inch (6.35 mm) Flare
Operating Temperature Range Cooling (Outdoor) 95°F (35°C) DB
Heating (Outdoor) 47°F (8°C) DB / 43°F (6°C) WB