Heat Pump Systems

CITY MULTI VRF - Indoor Units

PEFY (High Static)

Overview

The PEFY model is a high-performance, ceiling-concealed, ducted indoor unit that provides up to .80" external static pressure. An excellent choice for office buildings, schools, hotels, assisted-living facilities and other applications where ceiling space is available.

 

  • External static pressure settings are adjustable to meet different application conditions
  • Extremely quiet, with sound ratings as low as 34 dB(A)
  • Capacities range from 15,000 to 96,000 Btu/h
  • Side access to control panel
Model Specifications
Power Source Voltage, Phase, Cycle 208 / 230V, 1-phase, 60Hz
Cooling Capacity (Nominal) 15000 Btu/h (4.4 kW) *1
Power Input (Nominal) 0.188/0.207 kW *1
Heating Capacity (Nominal) 17000 Btu/h (5 kW) *1
Power Input (Nominal) 0.188/0.207 kW *1
Minimum Circuit Ampacity MCA 1.20/1.33 Ampere
Maximum fuse size (time delay) MOCP 15 Ampere
Recommended Fuse/Breaker Size 1.20/1.33 Ampere
Refrigerant Type R410A
Fan Motor type 1-phase induction motor
Airflow Rate 353-494 CFM (10.0-14.0 m³/min) *2
External Static Pressure (208V) N/A -0.20-0.64 In. WG (N/A -50-160 Pa)
(230V) 0.40 -0.60-0.80 In. WG (100 -150-200 Pa)
Air Filter Optional
Dimensions H x W x D Height 14-31/32 Inches (380 mm)
Width 29-17/32 Inches (750 mm)
Depth 35-7/16 Inches (900 mm)
Net Weight 98 Lbs. (44 kg)
Refrigerant Pipe Size O.D. Gas (Low Pressure) 1/2 Inch (12.7 mm) Flare
Liquid (High Pressure) 1/4 Inch (6.35 mm) Flare
Field Drainpipe Size O.D. 1-1/4 Inches (32 mm)
Operating Temperature Range Cooling (Outdoor) 95°F (35°C) DB
Heating (Outdoor) 47°F (8°C) DB / 43°F (6°C) WB